Suntube IV | GQG Single-Stage

Global Quality Series, available with 40,000 to 200,000 BTU/Hr.

Inputs and tube lengths from 10 to 70 feet. Solaronic single stage tube heaters can save up to 75% in energy costs compared to traditional climate control systems.Our premium quality infrared heaters are available, providing superior heat distribution and energy efficiency for a variety of commercial and industrial applications

For larger spaces, the commercial tube heater option provides efficient, targeted heating in warehouses, factories, and other industrial settings. This single-stage, corrosion-resistant tube heater offers our heat-treated aluminized swaged tube connection package, making it perfect for indoor and outdoor applications such as greenhouses, patios, and service garages, including harsh or corrosive environments. More information below.

 
4o
Find A Local Rep
Corrosion Resistant Infrared Heaters
  • Proven system design – over 30 years
  • 16 gauge titanium coated aluminized steel, heat-treated, combustion chamber
  • Corrosion resistant 16 gauge 4” O.D. aluminized steel, heat-treated, heat exchanger
  • Swaged tubes for easy installation
  • Simple chain mounting
  • CSA International Design Certified to ANSI/CGA Standards
  • Mill finish aluminum reflectors
  • 91.7% reflectional efficiency (shape)
  • Rotatable reflector arrangements of 0° or 30°
  • Burner fully assembled and tested – ready to hang
  • Factory installed wave turbulator for high efficiency

Safe, reliable operation

  • Durable direct spark ignition
  • 100% safety shut-off
  • Pre-purge cycle for safety
  • System validation light

Options:

  • Recessed Ceiling Kit
  • Side Reflector
  • 90° Elbow with Reflector
  • Common Vent Couplers
  • Inlet and Exhaust Kits
  • Blower Enclosure
  • 50 Hz for Worldwide Operation
  • Stainless Steel Construction

Manifold Operating Pressure
Natural Gas and LP/Propane:

  • 40,000 -100,000 BTU/Hr – 3. 5 inches WC
  • 105,000 -200,000 BTU/Hr – 5 inches WC

Minimum Inlet Pressure
Natural Gas:

  • 40,000 - 125,000 BTU/Hr – 6 inches WC
  • 130,000 - 200,000 BTU/Hr – 7 inches WC

LP/Propane:

  • All MBTUH – 11 inches WC

Maximum Inlet Pressure
Natural Gas and LP/Propane: 14 inches WC
1/2 inch FPT Gas Inlet

Electrical Rating
120 VAC – 60 Hz – 1 Phase
Blower: 1/24 h.p. motor
1.30 max. amp. draw at 138 cfm/free air

Warranty
10 year limited warranty on Burner Core
10 year limited warranty on All Combustion and Heat Exchanger tubes
2 year limited warranty on All Burner Controls